MITSUBISHI
Home >> Products >> MITSUBISHI >> R series PLC >> R series analog module >> R60TCTRT2TT2BW | MITSUBISHI Temperature control module R60TCTRT2TT2BW

R60TCTRT2TT2BW | MITSUBISHI Temperature control module R60TCTRT2TT2BW

MITSUBISHI R60TCTRT2TT2BW Manual And Instructions
R60TCTRT2TT2BW datasheetPDF datasheet

MITSUBISHI R60TCTRT2TT2BW Product information and technical parameters:
Brand: MITSUBISHI
Name: Temperature control module
Model: R60TCTRT2TT2BW
Analog input channel number: 4CH.
Available thermocouple: B, R, S, K, E, J, T, N, U, L, PL II, W5Re/W26Re.
Available temperature resistance: PT100, JPt100.
Sampling period 4CH: 250ms/500ms.
Control output cycle: 0.5s ~ 100.0s.
Input impedance: 1M.
Input filter (0: input filter OFF): 0 ~ 100s.
Sensor compensation value setting: the full range of the input range of the negative terminal to the full range of the input range.
Sensor input when the action: according to the scale of the processing.
Temperature control mode: ON/OFF PID pulse or 2 position control
Heater disconnection detection specification: there.
External wiring connection: 18 point screw terminal two.
Temperature tracking function can be monitored in real time.
Using Works3 GX in the temperature function, can be real-time tracking temperature, in the confirmation of the temperature waveform and parameter adjustment.
In addition, the temperature can be saved as a CSV file after the export, the use of a variety of purposes.
Module binding function.
Combined with the use of up to 64 sets of temperature control module for temperature control. Can be combined with the function of the following two points.
Heating function between modules.
Peak current suppression function between modules.
Temperature rising function between modules
By cooperating with the time of arrival of a number of loops, the average temperature is controlled.
Can realize the uniform temperature control, avoid partial burning control object,
Part of the phenomenon of thermal expansion. Can be divided into 16 groups, with its heating up to the time,
Reduce the overall system in heating up the waste of energy.

Output points: 32 points.
Output form: Transistor (source) output.
Rated open and close voltage, current: -.
Rated load voltage: DC12 ~ 24V.
Max load current: 0.1A/ point.
Response time: 1ms.
Common way: 32 point / public end.
Protection function (overload, overheat).
External wiring connection mode: 40 pin connector MITSUBISHI R60TCTRT2TT2BW.
Output module with mechanical relay contact mechanism,
Including the load voltage range of the relay and can be used for the output of the DC12~24V load transistor output type R60TCTRT2TT2BW
According to the load voltage, the output points of different, choose the most suitable user needs of the module.
Preventive maintenance based on the life of relay contact.
Relay output module can accumulate the number of ON of each output point MITSUBISHI R60TCTRT2TT2BW.
Through the understanding of the relay contacts of the number of times, according to the relay life of preventive maintenance. The input power supply voltage: AC100 ~ 240V.
Input frequency: 50/60Hz plus or minus 5%.
Input maximum apparent power: 130VA.
Maximum input power: -.
Rated output current (DC5V): 6.5A.
Rated output current (DC24V): -.
IQ-R MELSEC series consists of CPU module, power module, substrate module, input and output module, intelligent function module and so on MITSUBISHI R60TCTRT2TT2BW.
For the entire system, the substrate module can be expanded to 7 levels, up to 64 modules can be installed,
Therefore, large scale system can be constructed. In addition, by using the RQ extended substrate module,
The sea can also effectively use the MELSEC-Q series of modules of the asset. "Analog input channel number: 8CH.
accuracy
Ambient temperature of 25 plus or minus 5 degrees C: plus or minus 0.1%.
Ambient temperature 0 ~ 55 degrees C:-.
Temperature coefficient: positive and negative 35ppm/.
Common
Conversion speed: 10ms.
Insulation between channels: isolation transformer insulation.
Absolute maximum input: positive and negative 15V, 30mA.
External wiring connection mode: 40 pin connector.
Voltage input
The analog input voltage: DC - 10 - 10V.
Digital output value: 32000 ~ 32000.
Current input
Analog input current: DC0 ~ 20mA.
Digital output value: 0 ~ 32000.
Analog input module for the external analog signal into the interface of the programmable controller.
Can choose the channel between the insulation, voltage input, current input, voltage / current mixed input, thermocouple input, temperature resistance (RTD) input for a variety of purposes, such as modules.
Filter high frequency interference.
Analog input module has been equipped with a first order lag filter.
The analog input signal with high frequency interference component can be obtained by using the first order lag filter.
Parameters can be set through the filter time constant, no program can be easy to use.
Execute event driven program throuugh alarm output
Strengthen the implementation of the interrupt function according to the alarm output flag, easy to carry out preventive maintenance R60TCTRT2TT2BW.
The measured value and the change rate of the analog input signal exceed the upper and lower limits of the set,
Regardless of the procedure of the scan time, can be executed interrupt handling, quickly respond to abnormal conditions R60TCTRT2TT2BW.


...More relevant models >>>>