Analog input channel number: 4CH.
Available thermocouple: B, R, S, K, E, J, T, N, U, L, PL II, W5Re/W26Re.
Available temperature resistance: PT100, JPt100.
Sampling period 4CH: 250ms/500ms.
Control output cycle: 0.5s ~ 100.0s.
Input impedance: 1M.
Input filter (0: input filter OFF): 0 ~ 100s.
Sensor compensation value setting: the full range of the input range of the negative terminal to the full range of the input range R16ENCPU datasheet PDF catalog R16ENCPU PDF datasheet
R16ENCPU
Sensor input when the action: according to the scale of the processing.
Temperature control mode: ON/OFF PID pulse or 2 position control
Heater disconnection detection specification: there.
External wiring connection: 18 point screw terminal two.
Temperature tracking function can be monitored in real time R16ENCPU datasheet PDF catalog R16ENCPU PDF datasheet.
Using Works3 GX in the temperature function, can be real-time tracking temperature, in the confirmation of the temperature waveform and parameter adjustment.
In addition, the temperature can be saved as a CSV file after the export, the use of a variety of purposes.
Module binding function.
Combined with the use of up to 64 sets of temperature control module for temperature control R16ENCPU datasheet PDF catalog R16ENCPU PDF datasheet. Can be combined with the function of the following two points.
Heating function between modules.
Peak current suppression function between modules.
Temperature rising function between modules
By cooperating with the time of arrival of a number of loops, the average temperature is controlled.
Can realize the uniform temperature control, avoid partial burning control object,
Part of the phenomenon of thermal expansion. Can be divided into 16 groups, with its heating up to the time,
Reduce the overall system in heating up the waste of energy. Analog input channel number: 8CH.
accuracy
Ambient temperature of 25 plus or minus 5 degrees C: plus or minus 0.1%.
Ambient temperature 0 ~ 55 degrees C: plus or minus 0.3%.
Temperature coefficient.
Common
Conversion speed: 80 s/CH.
Channel to channel insulation.
Absolute maximum input: plus or minus 15V.
External wiring connection mode: 18 point screw terminal.
Voltage input
The analog input voltage: DC - 10 - 10V.
Digital output value: 32000 ~ 32000.
Current input
Analog input current: -.
Digital output value: -.
16 bit high resolution (1/32000).
No program can perform scaling and conversion operations.
The most suitable for the requirements of speed and accuracy of the detection equipment.
Easy to filter high frequency interference.
Execute event driven programs via alarm output.
Through the engineering software, the output of arbitrary analog waveform data.
Reduce downtime and reduce maintenance costs through anomaly detection
Works3 GX can be used to easily set the critical value of the inpput and output signals R16ENCPU datasheet PDF catalog R16ENCPU PDF datasheet.
Can quickly detect the abnormal signal, so it can shorten the downtime, reduce maintenance costs.
Channel insulation can ensure the accurate signal transceiver.
Model withh " -G " module in the channel between the insulation,
Isolation amplifiers are not required to prevent inter channel current and interference current R16ENCPU datasheet PDF catalog R16ENCPU PDF datasheet.